Why Do Evaporator Coils Freeze?

Frozen evaporator coil showing ice buildup and refrigerant flow restriction
Key Takeaways
  • Low evaporator pressure/temperature: Regardless of the root cause, a frozen coil always exhibits the same conditions – low pressure and low temperature in the evaporator
  • Three main causes: Evaporator freezing typically results from low refrigerant charge, insufficient airflow, or liquid line restrictions
  • Thaw before diagnosis: Always fully defrost the evaporator coil before attempting to troubleshoot the underlying issue
  • Prevention is key: Regular maintenance including filter changes, coil cleaning, and charge verification prevents most freezing issues

If you really want to understand this article in detail, I suggest reading the Refrigeration Cycle Explained before moving on. If you already have a firm grasp on the refrigeration cycle, stay and hang out for a bit.

An evaporator, as it pertains to the refrigeration cycle is the portion of the system where heat is absorbed from a medium. That medium could be air, water, glycol, or brine solution. For this article, we’ll focus on air.

Why Do Evaporator Coils Freeze?

As air passes over an evaporator coil, the evaporator absorbs heat. The entering air for example could be 75°F and the air leaving could be 55°F, which gives us a difference of 20°F or a delta t (temperature difference of the same medium) of 20°F.

This is just a generic example to show that as air passes over an evaporator coil, it removes heat from the air.

Now that we understand the function of an evaporator, we need to understand that it’s normal for an evaporator to freeze in some applications, like low-temperature refrigeration, where evaporator temperatures fall below freezing, 0°C or 32°F.

In these scenarios, the system is set up with a defrost cycle.

The defrost cycle is a time or temperature-initiated process that will shut down the refrigeration cycle. It will utilize electric heaters or diverted hot gas to melt and remove the ice from the coil.

In this article though, we will focus on air conditioning applications where a frozen evaporator is indeed problematic.

You need to remember something very important: no matter the cause of the freeze up, the isolated conditions in the evaporator will always remain constant, with low pressure and low temperature.

So, regardless of what’s happening upstream, a frozen coil will always look the same when looking at the evaporator conditions.

These conditions can vary however. We could see a system on the borderline of low pressure/temperature to well below freezing, but the end result will still be a frozen evaporator.

🔊 Check out this episode of the HVAC Know It All Podcast discussing “Why Evaporators Freeze”

The Common Causes

Let’s cover the well-known reasons an evaporator can freeze.

Low Refrigerant Charge

Simply put, the refrigerant charge is insufficient to bring the evaporator up to its normal running pressure.

Let’s use a 40-degree F. Saturated suction temperature or SST – this seems to be a common target.

It doesn’t matter the type of refrigerant. If you are trying to achieve a 40°F SST, then you’re trying to achieve a 40°F SST. Understanding how refrigerant properties work is crucial for proper system charging.

If we have a leak in a system or don’t add enough refrigerant on start-up or after a repair, we can freeze up if our evaporator SST begins to drop below 32°F.

Yes, we may have superheat. This added heat can bring the coil back up above freezing temporarily, but with a low charge, our system is running inefficiently and can create longer run times.

These longer run times, coupled with a drop in return air temperature, create a perfect storm for an evaporator to begin to freeze.

If all things are working as they should, a properly charged system will prevent freezing. Following proper refrigerant leak checking procedures is essential for maintaining correct charge levels.

In this Instagram post, I give some feedback on a low-charge issue where AC Smart Seal was used on a Liebert unit that had an evaporator micro leak.

[

View this post on Instagram

](https://www.instagram.com/p/CTA6BfTnfcs/?utm_source=ig_embed&utm_campaign=loading)

[A post shared by Gary McCreadie HVAC/R Tech/Business Owner (@hvacknowitall1)](https://www.instagram.com/p/CTA6BfTnfcs/?utm_source=ig_embed&utm_campaign=loading)

Lack of Air Flow

As airflow is reduced due to a dirty filter, plugged secondary heat exchanger (found on high-efficiency furnaces), ductwork issues, or a failing fan motor for example, it can lower the evaporator pressure/temperature.

This happens because there is not enough available heat to be absorbed from the slowly moving air.

In layman’s terms, the more heat there is to be absorbed, the higher the evaporator pressure and temperature.

The less heat there is to be absorbed, the lower the evaporator pressure and temperature.

This is why it’s important to ensure ductwork is designed properly and balanced.

It’s also equally important to ensure potential obstructions, like air filters and evaporator coils stay clean. Regular maintenance scheduling can prevent these airflow issues before they cause freezing problems.

The SUPCO Freeze Protection Control can be mounted on a suction line up to 7/8″ to provide freeze protection.

Freeze protection control

Liquid Line Restriction

A liquid line restriction is usually found within a liquid line filter drier or system metering device.

For example, if a filter drier starts collecting system debris and flow is reduced, a pressure drop is usually the culprit.

The pressure drop will cause a lower outlet pressure at the filter drier. If the pressure is low enough, the metering device will not receive a full column of liquid.

This, in turn, will cause a lower than normal evaporator pressure/temperature.

If that pressure/temperature relationship falls below 32°F then freezing may occur.

✅ TIP: If a liquid line filter drier has 2°F or more measured across it, we can presume it’s partially restricted and needs to be replaced.

If the metering device, which could be a capillary tube, fixed orifice, thermal expansion valve, or these days, an electronic expansion valve becomes blocked or restricted, it will most definitely create an excessive pressure drop. For heat pump systems, understanding bi-flow TXV operation is crucial for proper diagnosis.

Keep in mind that a pressure drop through a metering device is perfectly normal, but a pressure drop outside of design conditions that adds more restriction than needed will indeed cause lower evaporator pressure and temperatures than wanted.

Again, if that relationship falls beyond the freezing mark, frost/ice will start to form on the coil.

📺 In this short video, I cover a quick rundown of a thermal expansion valve. Subscribe to the channel if you enjoy the content.

Troubleshooting Frozen Evaporators

When you encounter a frozen evaporator, remember that diagnosis requires a systematic approach. The frozen coil is merely a symptom – your job is to find the root cause.

✅ TIP: In order to troubleshoot the issue, we must fully thaw the evaporator coil first before attempting to diagnose.

Once thawed, check these items in order:
1. Verify proper airflow (filters, blower operation, ductwork)
2. Check refrigerant charge and look for leaks
3. Inspect for liquid line restrictions (filter drier temperature drop)
4. Verify metering device operation

In Conclusion

Remember, all of the conditions we covered above will contribute to the same conclusion: low evaporator pressure and temperature relationships. If they become too low, freezing can occur.

It’s up to the service technician to determine the root cause of the freeze up and correct it. Whether it’s low charge, restricted airflow, or a liquid line restriction, the key is methodical diagnosis after completely thawing the coil.

Learn More with HVAC Know It All

For more technical content, check out the HVAC Know It All blog, the podcast, and our YouTube channel.

Share this article on:

Gary McCreadie

Gary McCreadie is an HVAC tech, the creator of hvacknowitall.com, the HVAC Know It All Podcast, and owner of McCreadie HVAC & Refrigeration Services

Follow us on:

Save 6% on purchases at TruTech Tools with code knowitall (excluding Fluke and Flir products)

Save 8% at eMotors Direct with code HVACKNOWITALL

Subscribe Now!

Subscribe now and stay up to date with the latest industry trends and HVAC tips and tricks!

Subscribe Now!

Subscribe now and stay up to date with the latest industry trends and HVAC tips and tricks!