Key Takeaways
- Specific Volume Matters: Refrigerant gas volume (ft³/lb) directly impacts compressor efficiency – “lighter and fluffier” gas requires more pumping to achieve the same cooling capacity
- SST Effects: Lowering Saturated Suction Temperature increases specific volume, reducing compressor capacity and COP while increasing discharge temperatures
- Superheat Impact: Excessive superheat returning to the compressor increases specific volume, causing higher operating temperatures and reduced system efficiency
- Pressure Enthalpy Diagrams: PE diagrams visually demonstrate how refrigerant properties change with temperature and pressure, essential for system optimization
Refrigerant Volume Matters
An often overlooked consideration in mechanical cooling systems is gas volume. Gas volume describes the cubic footage of space that a gas takes up per pound of the gas by weight (expressed in ft³/lb).
Consideration of refrigerant gas volume is most important when looking at refrigerant conditions in the suction line. The “lighter and fluffier” (coined by the author) that the gas is, the more of it your compressor must pump to accomplish 1 Ton of Cooling (12,000 BTU/hour). Understanding these properties is fundamental to how refrigerant works in extracting heat from air, even at low temperatures.
More specifically, volume is referred to as “Specific Volume.” For example, a Reciprocating Booster Compressor (1st of 2 compression stages) must have physically large cylinders to pump enough of the low temperature/high specific volume gas required to achieve its capacity.
Note that Booster Compressors pull a low SST (Saturated Suction Temperature) gas, perhaps -20°F SST, which has a high Specific Volume (SV). A gas with high Specific Volume is represented on the left side of the image below.

Understanding Density: The Opposite of Specific Volume
The opposite of specific volume is Density. Density (D) can be described as the weight of refrigerant in pounds per cubic foot of space the gas is taking up (expressed in lb/ft³). Air conditioning compressors pull suction from a high-temperature gas around 40°F SST, which is a very dense gas.
Using a Reciprocating Compressor again, its cylinders will be much smaller. This is for two reasons: 1. It needs to move less total refrigerant (since it is dense) to accomplish 1 Ton of Cooling 2. If the cylinders were large, the compressor would easily pull a high motor current as this dense (heavy and sluggish) gas takes more work to compress
The right side of the image above represents a gas with high density. Different compressors exist for different desired suction temperatures. When they’re represented mathematically, density and specific volume are reciprocal (image below).

Pressure Enthalpy Diagram Applications
For any compressor’s operation, the importance of gas volume can be clearly shown on a Pressure Enthalpy Diagram. The remainder of this article assumes the reader understands Pressure Enthalpy Diagrams and how refrigeration systems are plotted on them.
To learn these details or brush up on them, please visit Sporlan Pressure Enthalpy Diagram. This PDF is a great resource, which I reference regularly during classes on PE (Pressure Enthalpy).
Danfoss Cool Selector 2
The PE Diagrams shown in the remaining images are from the Danfoss Cool Selector 2 application. This free tool can be downloaded or viewed online.
Here is a video that shows (at 1:32) how to access PE Diagrams from Cool Selector. Within the application, they are referred to as “p-h” diagrams, with “h” representing enthalpy. You can also plot compressors/systems within the app (shown later in the video), select equipment, perform heat load calculations, and more.

Gas Volume Increases When SST Decreases
Picture your customer making a request to change the operating conditions of their cooler. They instead would like to run their cooler as a freezer. Something like this can be done by reducing the SST of the compressor which pulls suction on the refrigerated space’s evaporator.
If the LPCO (Low Pressure Cut-Out) is the compressor operating control, this switch could be operated to have the compressor turn off at a lower pressure corresponding to the new desired SST. To see the ill effects this could cause, we can use the Pressure Enthalpy Diagram. In the image below, an SST of 40°F and an SST of 0°F are both referenced on the 100% Saturated Vapour Line.
Their Specific Volume values (expressed in ft³/lb) are illustrated by the lines extending to the right side of the graph. It can be gleaned from this that a reduction in SST causes an increase in the Specific Volume of the refrigerant.
The characteristics of Saturated Vapour can be remembered by comparing them to freezing water: as the water freezes, it continues to expand. Mechanics and operators need to consider this increased gas specific volume when lowering the compressor SST.
Negative Effects of Reducing SST Due to Increased SV
- Increased SV: must pump more refrigerant per ton of cooling
- Increased gas entropy: less efficient compression
- Reduced hermetic motor cooling: though the gas is ‘colder’, its large volume results in less winding cooling
- Reduced volumetric efficiency
- Reduced compressor capacity
- Reduced COP (Coefficient of Performance)
- Increased compression ratio
- Higher discharge gas temperatures
- Higher oil temperatures

Gas Volume Increases with Higher Suction Superheat
A TXV (Thermostatic Expansion Valve) is a common, adjustable metering device that functions on the premise of an evaporator outlet superheat. In a basic system, a single compressor pulls a short suction line from the evaporator. For heat pump systems, understanding bi-flow TXV operation is crucial for proper refrigerant control in both heating and cooling modes.
If the TXV is adjusted incorrectly, it will constantly allow a higher-than-necessary superheat value to the compressor during operation. Superheat is required to be added to the refrigerant to ensure the compressor (a vapor pump) does not see refrigerant in its liquid state.
Any more superheat returning to the compressor than required is a system inefficiency. In the below Pressure Enthalpy Diagram, there are two plot points considered at an SST of -20°F for example. The first plot point represents a suction gas which has gained 60°F of superheat.
The second plot point shows an extreme amount of superheat added, totaling 180°F of superheat. What can be noticed is an increase in superheat returning to the compressor will also cause an increase in the Specific Volume of the return gas.
Characteristics of a Superheated Vapour can be remembered by comparing it to air: ‘hot’ air rises, as its volume increases. Note that a Saturated and a Superheated Vapour’s Specific Volume react in opposite ways to temperature change.
Understanding refrigerant properties like these is crucial for accurate system diagnostics. Property.com’s ‘Know Before You Go‘ tool helps HVAC professionals prepare for service calls by providing detailed property insights and equipment history. This preparation allows technicians to anticipate potential refrigerant-related issues before arriving on-site. Learn how Property.com helps HVAC pros optimize their service efficiency and close more deals.
How Excess Superheat Reduces System Efficiency
- Higher return gas temperatures
- Higher discharge gas temperatures
- Higher oil temperatures
- Factors due to SV increase caused by increased superheat:
- Less hermetic motor cooling
- Higher entropy of gas
- Reduced compressor capacity
- Reduced volumetric efficiency
- Reduced COP

Closing Thoughts
Two different things can put stress on a compressor, both by increasing the return gas specific volume: reducing SST and increasing superheat.
A Pressure Enthalpy Diagram can be a good way to visualize concepts like this while also applying metrics to the idea in the form of numbers. Understanding these principles is essential when performing proper heat load calculations to ensure systems are sized correctly for optimal efficiency.
If you can manage it, save light and fluffy for your desserts – not your refrigerant gas.