Key Takeaways:
- Two Discrete Capacity Levels: Two-Stage Scrolls operate at either 100% or 65% capacity, providing load-matching capability without variable speed drives
- Comfort-First Design: Longer run times at reduced capacity improve humidity removal and temperature consistency
- Field Identification: Look for the additional electrical box housing the Three-Way Solenoid Valve connections
- Cost-Effective Modulation: Delivers capacity control at significantly lower cost than Variable Speed options
One Compressor, Two Capacities
There are Single-Speed, Variable Speed Scrolls, and, most unique in the Scroll market, Two-Stage Scroll Compressors. In my 2nd of 3 articles in the series, we will cover Two-Stage Scrolls.
Most popular in this market is Copeland (article images courtesy of Copeland), offering the ability to run 100% capacity, or unload to 65% capacity with their “Digital” Scroll Technology. Internal Bypass Ports and related components can be seen in the cutaway image below.

In this writing, we will detail how Two-Stage Scrolls work and why they are a unique and valuable compressor in today’s market.
Loaded and Unloaded Operation
Capacity Control is an important topic related to Compressor Selection. The Two-Stage Scroll has a unique method of adjusting its Capacity utilizing its internal Three-Way Solenoid Valve. An example cross-section diagram is shown below.

The next image below represents the Compressor operating at 100% Capacity. This would represent the Compressor operating in response to “Full Load” conditions, and would run in this way until it has nearly met demand, often based on Suction Pressure. Once the Compressor has achieved matching capacity near demand, it will begin to unload to 65% Capacity.

To unload to 65%, this Two-Stage Scroll utilizes unloading in a method that I like to relate to Hot Gas Bypass. By activating the Three-Way Solenoid Valve at the desired Suction Pressure, the Lift Ring and Modulation Pin move to allow the Bypass Ports to open, so that some Compressed Gas is bypassed to avoid maximum compression. The compressor will run in this unloaded condition until it meets the required setpoint, at which point the compressor will turn off.
Traditional Hot Gas Bypass wastes energy by compressing refrigerant fully, then immediately decompressing it. Two-Stage Scrolls open Bypass Ports during compression itself – the motor does less work because less gas is fully compressed. This is why Two-Stage maintains high efficiency at part load. You may still encounter Hot Gas Bypass on older commercial equipment; Two-Stage is often the modern replacement solution.
When Does Unloading Occur?
What triggers the transition from 100% to 65%? Typically suction pressure control. As pressure drops toward setpoint, the controller energizes the solenoid to unload. Some applications use supply air temperature control instead. During transition, the Lift Ring repositions within seconds while the motor continues at full speed.
Podcast Episode: For more on Two-Stage vs Variable Speed operation, listen to the HVAC Know It All podcast with Joshua Souders from Copeland (January 2025).
Two-Stage vs Digital Scroll vs Variable Speed
These terms are often confused. They represent distinct technologies:
Two-Stage Scrolls operate at two discrete levels (100% and 65%) controlled by a solenoid valve. The motor runs at constant speed.
Digital Scrolls provide continuous modulation (10-100%) by rapidly cycling a solenoid to repeatedly load and unload the scroll mechanism in 20-second cycles. Effective capacity equals the loaded/unloaded time ratio.
Variable Speed Scrolls modulate capacity (15-120%) by changing motor speed via a VFD. Highest efficiency, but adds cost and complexity.
Quick Comparison
| Feature | Two-Stage | Digital Scroll | Variable Speed |
|---|---|---|---|
| Capacity Range | 65% – 100% | 10% – 100% | 15% – 120% |
| Modulation Type | 2 discrete steps | Continuous (PWM) | Continuous (VFD) |
| Motor Speed | Constant | Constant | Variable |
| Relative Cost | Lowest | Medium | Highest |
| Part-Load Efficiency | Good | Better | Best |
For most residential applications, Two-Stage provides the best balance of comfort, cost, and reliability.
Comfort Benefits and Humidity Control
Single-speed compressors cycle frequently on mild days – sometimes every 10-15 minutes. Short run times mean reduced dehumidification (the coil never reaches peak moisture removal) and temperature swings as the system cycles.

By unloading to 65%, Two-Stage Scrolls run longer when single-speed would shut off. The evaporator stays cold longer, removing more moisture and keeping indoor dew point consistent. Fewer cycles also reduce contactor wear and inrush current events.
To verify: monitor indoor humidity over several days, observe run times on mild days, and compare amp draw between loaded and unloaded modes. Two-Stage equipment is a compelling upgrade for customers complaining about humidity despite adequate cooling.
Troubleshooting Two-Stage Scroll Compressors
Two-Stage Scrolls share most failure modes with single-speed scrolls, but the modulation system adds diagnostic considerations.
Verifying Unload Operation
The most common issue is failure to unload (stuck at 100%) or load (stuck at 65%). To verify:
- Check solenoid voltage during unload call. No voltage indicates upstream control issue
- Listen for the click when solenoid energizes
- Monitor suction pressure (should rise slightly when unloaded)
- Compare amp draw between modes (should be measurably different)
Solenoid Valve Failures
Stuck loaded (solenoid fails closed): compressor runs 100% only, may short-cycle on mild days. Stuck unloaded (solenoid fails open): cannot reach full capacity, struggles on high-load days. When replacing, follow proper brazing procedures to prevent contamination.
Internal components (Lift Ring, Modulation Pin) cannot be field-serviced. If the solenoid operates correctly but modulation doesn’t occur, compressor replacement is required.
From Youtube: Gary discusses installation and failure prevention guidance, listen to the HVAC Know It All podcast with Jeff Kukert on Scroll Compressor Best Install Practices (July 2024).
Using CoreSense Diagnostics
Many Copeland Two-Stage Scrolls include CoreSense protection. The Copeland Mobile app decodes flash codes and provides discharge temperature history, cycling events, and protection trips. Always check CoreSense data first – it often points directly to root cause.
Application of Two-Stage Scrolls
Two-Stage Scroll Compressors are utilized in modern Domestic, Commercial, and Industrial Refrigeration and Air Conditioning applications.
Their great benefit is operating with a Capacity Control built into the Compressor, allowing for full load or part load operation.
Although they do not offer the precise control that a Variable Speed Scroll does, they come at a significantly lower purchase cost since a Variable Speed Drive does not need to be purchased along with the compressor.
Two-Stage typically adds 15-25% to compressor cost versus single-speed, while Variable Speed adds 40-60% or more including the VFD. Two-Stage requires only an additional control wire; Variable Speed needs proper VFD mounting and often electrical upgrades. For most residential applications, Two-Stage provides meaningful improvement while keeping cost and complexity reasonable.
Copeland’s next-generation Two-Stage compressors are optimized for R-454B and R-32. When working with A2L systems, remember that charging procedures and leak detection requirements differ from R-410A.
From Instagram: Gary discusses Copeland 2-stage scroll compressors for residential applications, explaining 65%/100% capacity operation.
Physical Appearance: Copeland Two-Stage Scroll

In the image above, you can see the traditional-looking Electrical Terminal Box for a Copeland Scroll open on the right side. Besides the three terminals for 3-phase wiring, this box also has Copeland’s CoreSense module.
On the left side of the above image, there is an additional Electrical Box for the Two-Stage Scroll. The image shows this box opened. Inside of this are the electrical connections for the Three-Way Solenoid Valve.

This dual-box configuration is your most reliable visual indicator. Single-speed scrolls have only the main terminal box; Variable Speed scrolls connect to an external VFD.
Summary
Two-Stage Scrolls occupy valuable middle ground – delivering capacity modulation without Variable Speed cost and complexity. Consider them for residential replacements where customers complain about humidity, light commercial applications with variable loads, and A2L transition installations where simpler technology reduces risk.