Refrigerant Recovery

Refrigerant recovery system setup and equipment
Key Takeaways
  • Two Recovery Methods: Direct recovery is standard for all jobs, while push/pull is faster for systems with 15+ pounds of refrigerant
  • Valve Core Removal: The single most effective speed improvement – removes the biggest restriction in your recovery setup
  • Temperature Management: Cooling the recovery cylinder and refrigerant significantly speeds up the process by maintaining pressure differential
  • Safety First: Always purge hoses of air, never fill cylinders beyond 80%, and follow proper EPA recovery requirements

Step-By-Step Refrigerant Recovery Process

I often see new techs asking how to recover or experienced techs asking how to recover faster, so let’s look at both.

If you are looking to connect with a strong culture of HVAC technicians, check out the subscription-based HVAC Know It All app. This all originated from some personal trial and error when an air conditioning manufacturer I worked for had a recall – a missing Schrader core at the receiver service valve (king valve), of all things.

This was a possible disaster for an unsuspecting tech. Remove the cap expecting a valve core, and well… Not fun.

So it was time to install a single valve core in 50 operational units in critical spaces, each holding between 50 and 100 pounds of R-410A. I had a reasonably repeatable situation on my hands, and I had the opportunity to try all sorts of things, such as the size of the recovery cylinder, the size of the hose, and the type of hose.

I’ll cover all this at the bottom of this article, but we’ve got to start with the basics!

How Do We Recover?

There are two typical methods: direct recovery and push/pull. Before starting any recovery work, it’s crucial to understand proper system evacuation procedures that you’ll need after completing repairs.

You should always familiarize yourself with the equipment you are working with, but I’ve included a simple diagram of how to connect the required equipment and a “step-by-step” guide for the newer techs.

Direct Recovery

This is our typical recovery method, which will be how every recovery task will finish.

typical recovery method
[

View this post on Instagram

](https://www.instagram.com/p/CG2caV7LGMD/?utm_source=ig_embed&utm_campaign=loading)

[A post shared by Gary McCreadie HVAC/R Tech/Business Owner (@hvacknowitall1)](https://www.instagram.com/p/CG2caV7LGMD/?utm_source=ig_embed&utm_campaign=loading)

Push/Pull Recovery

This will be your faster option if the system has 15 or more pounds of refrigerant. The more refrigerant the system holds, the more time you’ll save.

✅ PRO TIP: Using an inline sight glass during push-pull recovery will allow you to visually determine when the liquid flow has stopped.

Refrigerant Recovery Process

Now Let’s Speed It Up…

Valve Core Removal Tools

If you were only going to change one thing – this is it! If you’re stuck pulling through valve cores, get two of these. They’ll even help speed up your evacuation.

Recovery Cylinder

  • Make sure the cylinder is clean and has been evacuated to 500 microns or less. And NEVER fill beyond 80%. This allows for the expansion of the refrigerant.
  • If it’s practical, use a larger cylinder; this will make the recovery go quicker.

Hoses

  • Avoid hoses with “anti-blowback” or “low loss” style fittings.
  • Standard hoses are ¼” – using larger diameter hoses will get you faster recovery. They’re often marketed as “heavy duty,” “charging,” or “vacuum” hoses.
  • Use hoses that are as short as possible.

Temperature Management

  • Cool down the recovery cylinder – this will drop the pressure of the recovery cylinder.
  • With many recovery machines, you can use the fan to draw air over the recovery tank.
  • Water will work even better, but you’ll need water flow.
  • Cool down the refrigerant! This one tends to be your best bet if you’re dealing with large volumes of refrigerant – there are heat exchangers available just for this purpose.

Filter It!

If you suspect the system refrigerant to be dirty, use an inline filter drier at the inlet to the recovery machine.

With methods ranging from nothing new required to a whole new rig for recovery, you’ve got choices to speed up your recovery in just about all applications. Give some of these a try and see how they work for you.

Categories:
Share this article on:

Dan Reggi

Humber College Professor

Follow us on:

Save 6% on purchases at TruTech Tools with code knowitall (excluding Fluke and Flir products)

Save 8% at eMotors Direct with code HVACKNOWITALL

Subscribe Now!

Subscribe now and stay up to date with the latest industry trends and HVAC tips and tricks!

Subscribe Now!

Subscribe now and stay up to date with the latest industry trends and HVAC tips and tricks!