Key Takeaways
- Pump Down Purpose: Prevents liquid refrigerant migration to the compressor during off-cycles, avoiding potentially damaging liquid slugging on startup
- Two Circuit Types: Recycling pump down provides maximum protection but increases compressor starts, while non-recycling reduces starts but risks liquid in the sump
- Critical Components: System requires a solenoid valve in the liquid line and low-pressure switch (LPS) to control the automated pump down sequence
- Safety First: Manual pump down using the King valve is possible but requires thorough understanding to prevent component damage
Pumping down a refrigerant circuit is a great way to avoid liquid migration back to the compressor during off-cycles. The refrigerant will naturally equalize and move to the section of the system with the lowest ambient temperature.
If that section happens to be anywhere on the low side of the system, we could potentially have a liquid slug on start-up. This situation can cause serious compressor damage and system failure.
What is a Pump Down Anyway?
A system pump down utilizes a solenoid valve in the liquid line; when the system set-point temperature has been satisfied, the solenoid valve will close. The compressor will continue to pump refrigerant into the condenser and/or receiver, drawing it from the low side of the system.
The condenser or receiver, or a combination of both, must be designed to hold the entire charge of the system. The compressor operation will cut out once the pre-determined set point of the low-pressure switch, or LPS for short, has been reached.
The LPS cut-out setting will be directly related to the application and/or refrigerant used. In reverse, on a call for cooling, the solenoid valve will open. The refrigerant will travel into the low side of the system due to the pressure difference between the two sides.
Once the pre-determined LPS cut-in set-point has been reached, the compressor will start and resume normal operation. Again, the cut-in setting is directly related to the application and/or refrigerant being used.
In most cases, this order of operations is automatic and wired as such to perform this task.
A manual pump down can also be performed on many systems if a solenoid valve is not present by manually closing the King valve (valve at the receiver outlet), for example. Before attempting this method, ensure that you fully understand this procedure, as damage to system components can occur if performed incorrectly.
Recycling Pump Down
There are two types of pump down circuits, electrically speaking. This is in regard to the way they are wired to operate.
The first is the “Recycling Pump Down” circuit. The method of pump down is still the same, using an LPS and solenoid valve. However, if on the off cycle refrigerant is able to creep by internally leaking solenoid valves or compressor valve plates, this will increase the low side pressure closing the LPS.
In this case, the compressor will start and perform a pump down during the off cycle to ensure that liquid migration is not taking place. Understanding how refrigerant properties enable heat transfer helps explain why refrigerant naturally migrates to cooler areas of the system.
A disadvantage with this style of pump down is the potential for increased compressor starts over time. The clear advantage is that your compressor will never start loaded with liquid in the sump.

Diagram courtesy of refrigerationbasics.com
Non-Recycling Pump Down
The second type is the “Non-Recycling Pump Down” circuit. Again, the method of pump down is still the same. In this case, if there is any refrigerant migration during the off-cycle, the compressor will not start and perform a pump down.
Notice the normally open switch (Hold) that will not allow the compressor to restart on the off cycle. The system thermostat must be calling (in the closed position) for the compressor to begin operating.
The LPS will still close if valves are internally leaking, but the compressor will not start until there is a call for cooling. A direct disadvantage of this method is quite apparent. The compressor may start with liquid refrigerant present in the sump. On the other hand, there is the potential for fewer total compressor starts.

Diagram courtesy of refrigerationbasics.com
Choosing the Right Pump Down Method
Most systems I have worked on through the years have utilized a “Recycling Pump Down.” I find this to be a superior method to protect the system from catastrophic failure. Many of you might say, “why not replace the internally leaking parts?”
This can be costly on large systems, especially if there are multiple parts in question. In a perfect world, all parts would be sealed tight, and the fear of internal leak issues would not be a factor. When dealing with effective refrigerant leak checking methods, remember that internal leaks can be just as problematic as external ones.
The “Recycling Pump Down” is designed for the inevitable that we all experience daily, flaws upon flaws from system to system. One recommendation I would make is to employ an adjustable low-pressure switch; this way, you are in control and can adjust the pump down cut-in and cut-out as necessary.
Comparison of Pump Down Methods
| Feature | Recycling Pump Down | Non-Recycling Pump Down |
|———|——————-|————————|
| Compressor Protection | Maximum – Never starts with liquid | Limited – May start with liquid present |
| Compressor Starts | Higher frequency | Lower frequency |
| Off-Cycle Operation | Compressor cycles as needed | Compressor remains off |
| Control Complexity | Standard wiring | Requires hold switch circuit |
| Best Application | Critical systems, variable ambient conditions | Stable environments, less critical applications |
View this post on Instagram<div style="background-color: #F4F4F4; height: 12.5px; transform: rotate(-45deg) translateX(3px) translateY(1px); width: 12.5px; flex-grow: 0; margin-right: 14px; margin-left:Categories:
Gary McCreadie
Gary McCreadie is an HVAC tech, the creator of hvacknowitall.com, the HVAC Know It All Podcast, and owner of McCreadie HVAC & Refrigeration Services
Follow us on:
Save 6% on purchases at TruTech Tools with code knowitall (excluding Fluke and Flir products)
Save 8% at eMotors Direct with code HVACKNOWITALL
About Our Blog
HVAC Know It All was created by Gary McCreadie, a licensed refrigeration and gas technician, with three goals in mind:
Learn. Teach. Entertain.
All within a positive environment.Happy HVACing…
Search
Recent Posts
Categories
Business Growth (54) Components (27) Troubleshooting (24) Heat Pumps (23) Heating Systems (21) Air Conditioning (19) Career in the Trades (17) Refrigerants (16) Refrigeration (15) Tools and Equipment (15) Education (15) Safety (13) HVAC Maintenance (11) HVAC Installation (10) Customer Service (10) A2L (8) Compressor Issues (7) Electrical (7) Commercial Systems (6) Marketing (4) Humidity Control (4) Airflow (4) Automation (4) Industry Trends (4) Design (3) Specialized HVAC (3) Indoor Air Quality (3)