Carbon Monoxide Testing and CO Action Limits

carbon monoxide testing
Key Takeaways
  • Silent Killer: Carbon monoxide is odorless, colorless, and poisonous – requiring professional testing equipment to detect dangerous levels
  • Test Every Call: HVAC technicians should test for CO on every service call using properly calibrated instruments at multiple test points
  • Action Limits: Normal CO levels should be under 50 ppm in flue gas for modern appliances, with 200 ppm as the maximum safe operating limit
  • Safety First: Any ambient CO reading above 6 ppm requires immediate investigation, and readings above 70 ppm can cause acute health effects

Carbon monoxide is an odorless, colorless, poisonous gas that is a natural and common product of combustion of all kinds.

Most gas-burning furnaces normally produce carbon monoxide as a part of their operation. When all systems are operating normally, that toxic gas goes harmlessly up the flue.

Unfortunately, many people are injured or killed from exposure to toxic levels of carbon monoxide that are traced back to a malfunctioning combustion appliance.

Next to the fire department, HVAC technicians are on the front lines in the battle to keep the public safe from dangerous carbon monoxide. Just as we follow proper maintenance schedules to prevent winter heating failures, CO testing should be part of every technician’s routine safety protocol.

Technicians need to be prepared with the best equipment and techniques and test for carbon monoxide on every call. The following are some guidelines on test instrument selection and application that all technicians will benefit from.

Carbon Monoxide’s Effect on the Human Body

carbon monoxide danger sign

Carbon Monoxide (known as CO) is poisonous.

When inhaled, it bonds to the red blood cells in the body and prevents oxygen from being absorbed. As a result, internal organs and cells are unable to get the oxygen they need to survive, and they begin to suffer.

The higher the concentration of CO in the blood, the worse the problem is, and organs suffocate from lack of oxygen.

Extraordinarily little CO is needed to be harmful. Its concentration is normally measured in parts per million (ppm).

Air is normally 20% oxygen. Measured in ppm, oxygen would be about 200,000 parts per million.

A concentration of 70 ppm of CO is enough to produce acute negative effects in healthy adults. A concentration of 400 ppm of CO is enough to produce unconsciousness and death over just a couple of hours of exposure.

Because carbon monoxide has no taste, no color, and no smell, most people who are exposed don’t even know it. For this reason, it is known as the “silent killer,” and many people die in their sleep.

In the event of carbon monoxide exposure, victims must be removed from the toxic environment and allowed to breathe fresh air. Natural respiration will release CO from the blood and allow normal oxygen uptake to resume over time.

If the victim is unconscious or non-responsive, call 911 immediately!

Here is a video discussing CO facts and a personal CO meter by UEI:

Carbon Monoxide Production

In a normal and perfect combustion process, molecules of fuel and air combine to create Carbon Dioxide (CO2) and Water Vapor (H2O).

In most fuel burning appliances, the combustion process is not quite perfect. Instead of oxygen and carbon combining perfectly, a single carbon atom will combine with one oxygen atom and CO will be the result.

The worse the combustion process is, the greater the concentration of CO in the flue gases. This is similar to how improper system operation can lead to other issues, like those we see when troubleshooting heat pump reversing valves or dealing with combustion air problems.

As long as the appliance is venting and drafting normally, this toxic gas goes harmlessly up the flue. If there is a problem with the flue, combustion air supply, fuel delivery, burner, or heat exchanger, flue products can mix with the ambient air of the home, causing a dangerous condition.

When this happens, carbon monoxide production will usually worsen as the combustion air supply is now contaminated with flue products instead of fresh, pure air.

To protect against this situation, technicians must test for carbon monoxide on every call and take steps to ensure its production is within normal levels and that the appliance is operating normally.

Since carbon monoxide is invisible, you won’t know it is there until you test. If you test frequently, you will notice that systems you would never expect to be a hazard may be a ticking time bomb.

Test Instruments

There are three major types of professional grade instruments available for testing carbon monoxide.

Ambient Testers

Ambient carbon monoxide testers are small handheld units that can fit in a shirt pocket. They combine a CO sensor and a digital display.

The sensor is exposed to the ambient room air, and as carbon monoxide contacts the sensor, the display reads the concentration in parts per million.

These types of testers are popular due to their relatively low price (approximately $200 USD) and ease of use. Unfortunately, these devices cannot be used to test raw flue products or warm air streams like the supply register of a forced air furnace.

Pump-Driven Single Gas CO Analyzers

These handheld units feature a flue probe and an onboard pump used to draw in a measured sample air stream and flow it across the sensor. They are ideal for ambient testing as well as for sampling warm supply air streams and for testing the flue products of operating fuel fired appliances.

An LCD screen displays the amount of CO. Some units will graph CO measurements over time, can store readings, and can interface with a printer to provide a permanent record of the measurements.

These instruments generally cost between $450 and $500 USD.

Combustion Analyzers

Full blown combustion analyzers will sample the oxygen content as well as carbon monoxide and temperature of flue gases. They will also calculate the concentration of CO2 as well as excess air and combustion efficiency.

Combustion analyzers that have a CO feature can be used like the single gas analyzers described above to test ambient and supply air CO levels. When performing comprehensive system diagnostics, these analyzers complement other essential tools used in proper heat load calculations to ensure systems are properly sized and operating safely.

Full-feature combustion analyzers start at about $600 and can go up to $2000 as features and reportability increase.

Recommended Test Points and CO Levels

All CO test instruments must be zeroed in fresh air before testing begins. Once zeroed, these are the test points technicians should check:

Ambient Air

Walk into the house with your CO meter on and sampling. Look for any increase in the reading as you enter the home and walk around.

Any measurement above zero is not normal. Carbon monoxide is only present as a byproduct of combustion.

In homes where people smoke tobacco or burn scented candles, it is common to measure CO concentrations between 2 ppm and 6 ppm. Any measurement above 6 ppm should be considered unusual, and the cause must be investigated.

Mechanical Room

The area around the fuel burning appliances should also be tested. The readings should be no more than in the ambient air of the home.

Appliance Vestibule and Burner Area

Here again, the readings should be zero, the same as in the ambient air. All airflow should be moving into the burners and heat exchanger, and all flue products should be moving in that direction also.

Any increase in reading here will indicate that combustion products are moving in the wrong direction.

Supply Air Stream in the Plenum

In the supply air stream in the plenum of a warm air furnace, any increase in reading may indicate that combustion products are escaping the heat exchanger and joining the air stream to be distributed by the blower.

Undiluted Flue Gas

A measurement of CO in the undiluted flue gas of an appliance is a good indicator of the quality of combustion.

| Appliance Type | Normal CO Range | Maximum Safe Limit |

|—|—|—|

| Modern Gas Appliances | < 50 ppm | 200 ppm |

| High Efficiency Boilers | Up to 175 ppm | 200 ppm |

| Older Natural Draft | Up to 200 ppm | 200 ppm |

| Red Tag Limit (Utilities) | – | 400 ppm |

Under no circumstances should an appliance be allowed to operate at CO levels higher than 200 ppm without adjustment or repair. Most gas utility suppliers will red tag an appliance when the flue gas CO levels exceed 400 ppm.

Final Thoughts on Carbon Monoxide Testing

Remember that all professional CO instruments require annual calibration and certification. Testing with an instrument that has out of date calibration can open you up to significant liability if that causes you to miss an ongoing hazardous CO situation.

Just as [commercial HVAC systems require strategic maintenance planning](https://hvacknowitall.com/blog/the

Share this article on:

Eric Shidell

Eric Shidell is a veteran high-level HVAC service and diagnostic technician, professional mentor, and trainer.  He is a pioneer of distance learning for the mechanical trades.  He helps HVAC contractors across North America enhance the performance of field technicians through intermediate and advanced technical training programs.  Learn more at www.hvacservicementor.com or email Eric at eric@hvacservicementor.com.  Contact by phone at 719-425-9860.

Follow us on:

Save 6% on purchases at TruTech Tools with code knowitall (excluding Fluke and Flir products)

Save 8% at eMotors Direct with code HVACKNOWITALL

Subscribe Now!

Subscribe now and stay up to date with the latest industry trends and HVAC tips and tricks!

Subscribe Now!

Subscribe now and stay up to date with the latest industry trends and HVAC tips and tricks!